PWRM Power Exhaust motors should be set to 1
(4 motors) for the 020-050 units and 2
(6 motors) for the 060 unit
In the CONFIGURATION-BP submenu set the following
variables:
BP.SL Modulating PE Alg Select to 2
BP.S Building Pressure sensor to enable
BP.R Building pressure sensor range to 0.25
BP.HP High BP level to desired value
BP.LP Low BP level to the desired value
OPERATION
The control system has many options and accessories as
well configurable control options. Actual unit operation will
depend on the selected options and set points, but the following
is a general sequence of operation for the basic types of
systems.
Cooling, Constant Volume (CV) Units On power
up, the control module will activate the initialization software.
The initialization software will determine the unit configura-
tion and also initialize any controls loops and input/output
devices. All configuration settings are maintained in memory
during power outages. All alarms are be maintained in memory
and must be cleared through the Scrolling Marquee display.
CONSTANT VOLUME CONVENTIONAL THERMO-
STAT CONTROL If the unit is equipped with a conven-
tional thermostat (with Y1, Y2, W1, W2 and G connections)
then the control will perform the following sequence.
When G is closed, the indoor fan will turn on. The G
connection must be closed for heating or cooling to occur. If
the unit is in the occupied mode then the economizer dampers
will be opened to the minimum economizer position. If the unit
is in the unoccupied mode then the economizer dampers will
remain fully closed.
If Y1 is closed, then the control will first check the ability to
use the economizer. If the economizer can be used, based on
the selected changeover configuration, then the control will
modulate the damper open to maintain the low load economiz-
er leaving air temperature set point. If Y2 closes then the
control will lower the leaving air temperature set point to the
configured high load set point. If the economizer cannot satisfy
the load, then compressors will be sequenced on to maintain
either the low or high load temperature set points. If the
economizer cannot be used or the enable control disables the
economizer, then the control will sequence the compressors
based on the Y1, Y2 signals. If two-stage control has been se-
lected, then the control will map the compressors to the Y1, Y2
inputs as defined in the loading sequence. If multistage control
has been selected, then the control will add and remove
compressors stages to maintain the high and low demand set
points. If Y1 is closed, at least one compressor stage will be
turned on.
If W1 closes, then it will indicate that the unit should be in
the heating mode. If the unit is equipped with gas or electric
heat then the first stage of heat will be energized. If W2 closes,
then the control will turn on the second stage of heat. If the unit
is equipped with a staged gas heat control option, then the W1
and W2 signal will be used to control the gas heat to the config-
urable high and low heat load leaving air temperature set
points. If the unit is equipped with gas heat, then the IGC board
will control the operation of the gas heat. See the section on the
IGC board sequence of operation.
CONSTANT VOLUME SPACE SENSOR CONTROL — If
the space temperature operation has been selected by using a
T55, T56, or T58 sensor, then following logic will be used to
control the operation of the unit. If a space temperature sensor
is used, then a wire jumper must be added between R, W1, and
W2 for the heat to operate.
If a remote switch option is being used and configured for
start/stop, then the switch must be closed for the unit to operate.
If the remote switch option has been configured for occupancy,
then the switch will be used to control occupied and unoccu-
pied mode. In the unoccupied mode, the economizer damper
will be positioned to zero unless free cooling is being used. In
the occupied mode, the damper will open to the minimum posi-
tion unless IAQ control is in also being used and then might be
controlled to a lower position. When in the unoccupied mode,
the type of cooling can be configured. If the internal timeclock
function is being used, the start/stop function and occupied and
unoccupied control will be established by the schedules that
have been selected.
There are also some special pre-occupancy modes that may
be used. If Temperature Compensated Start is active, the unit
will be controlled as in the occupied mode and will start at a
time (as determined by prior operation) to have the space at set
point by the occupied time. If the unit has been configured for a
pre-occupancy purge, then the control will start the unit in vent
mode prior to the occupancy time to vent the space. If an IAQ
sensor is being used and the low IAQ set point is satisfied then
the occupancy purge mode will be terminated.
When using the space sensor control option, the set points
for heating and cooling are configurable through the Scrolling
Marquee display. If a T56 sensor is being used, then the set
point can be shifted by as much as 10 degrees. If the space
temperature goes above the cooling set point, then the unit will
go into cooling mode. If the economizer can be used, then the
control will first try to control to the leaving air temperature set
point. The leaving air set point will depend on the space
temperature. If the temperature is above the low demand set
point then the low economizer load discharge air temperature
set point will be used. If the temperature is above the high load
space temperature set point then the high load leaving air
temperature set point will be used. If the economizer cannot
satisfy the load, then compressors will be sequenced on to
maintain either the low or high load temperature set points. If
the economizer cannot be used or the enable control disables
the economizer, then the control will sequence the compressors
based on the high and low load space temperature variables. If
two stage control has been selected, then the control will map
the compressors to the low and high loads as defined in the
loading sequence. If adaptive mode has been selected, then the
control will add and remove compressors stages to maintain
the high and low demand leaving air set points.
If the load goes below the heating space temperature set
point, then it will indicate that the unit should be in the heating
mode. The economizer will be closed to the minimum position
and, if the unit is equipped with gas or electric heat, then the
first stage of heat will be energized. If the space temperature
goes below the high load space temperature set point, then the
control will turn on the second stage of heat. If the unit is
equipped with a staged gas heat control option, then the low
load and high load demand signal will control the leaving
air temperature set point and will turn on heating stages to
maintain the leaving air temperature set points.
If the units is configured for unoccupied free cooling,
mechanical cooling, or heating and the temperature goes
beyond the unoccupied configuration set points then the
control will turn on free cooling, mechanical cooling, or heat as
need to return within the unoccupied set points. When in this
mode, the economizer dampers will be maintained fully closed
or to the minimum unoccupied ventilation set point.
Variable Air Volume Control — On power up, the
control module will activate the initialization software. The
initialization software will determine the unit configuration and
also initialize any controls loops and input/output devices. All
configuration settings are maintained in memory during power
outages. All alarms will be maintained in memory and must be
cleared through the Scrolling Marquee display.