APPENDIX A — CCN POINTS
BLDGPRES — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display BP Building Pressure NO X.XXX in H2O -0.25 TO 0.25 PRESSURES BLDG
Status Display SFS Supply Fan Status Input YES ON/OFF — On/Off INPUT FAN.S
Status Display SFAN Supply Fan State YES ON/OFF — On/Off OUTPUTS S.FAN
Status Display ECONOCMD Econo Damper Command Pos YES XXX % 0 to 100% OUTPUTS E.PWR
Status Display ECONOPOS Econo Damper Current Pos NO XXX % 0 to 100% OUTPUTS EC.AP
Status Display ECONOMIN Economizer Min.Position YES XXX % 0 to 100% CONFIGURATION MIN.P
Status Display IAQMINP IAQ Demand Vent Min.Pos. YES XXX % 0 to 100% CONFIGURATION AQ.MP
Status Display PE_A Power Exhaust Stage A NO ON/OFF — On/Off OUTPUTS PE.A
Status Display PE_B Power Exhaust Stage B NO ON/OFF — On/Off OUTPUTS PE.B
Status Display PE_C Power Exhaust Stage C NO ON/OFF — On/Off OUTPUTS PE.C
Status Display BPSMZ BP Load Factor NO XXX — 0-100% PRESSURES BPSZ
Status Display BPRISE BP Rise Per Stage NO X.XXX — -50 TO 50 — —
Status Display BPINT BP PID/Integral term NO X.XXX — -10 to +10 PRESSURES BP.IT
Status Display BPZ BP PID Threshold NO X.XXX — 10 to +10 — —
Status Display BPY BP Deadband NO X.XXX — 10 to +10 — —
Status Display BPERROR Building Pressure Error NO X.XXX — -0.75 to +0.75 PRESSURES BLDG
Status Display BPRATE Rate of Chng of BPERROR NO X.XXX — -10 to +10 — —
Status Display BPHPOVRD High BP Override YES XXX — On/Off CONFIGURATION BP.HP
Status Display BPLPOVRD Low BP Override YES XXX — On/Off CONFIGURATION BP.LP
CAPACITY — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display SMZ Capacity Load Factor NO XXX % -100 TO +100 RUN STATUS LOD.F
Status Display RISE_PCT Rise Per Percent Cpcty NO XX.XX — 0-100% — —
Status Display ADDRISE Next Stage EDT Decrease NO XX.XX F 0 TO 30 — —
Status Display SUBRISE Next Stage EDT Increase NO XX.XX F 30 TO 0 — —
Status Display Z_PLUS Cap Threshold Adding NO XXX.X — 0 TO 125 — —
Status Display Y_PLUS Cap Deadband Adding NO XXX.X F 0 TO 10 — —
Status Display Y_MINUS Cap Deadband Subtracting NO XXX.X F 10 TO 0 — —
Status Display Z_MINUS Cap Threshold Subtracting NO XXX.X — -0 TO -125 — —
Status Display COOLCPNT Cooling Control Point YES XXX.X F 45 TO 90 — —
Status Display MAT Mixed Air Temperature YES XXX.X F -40 TO 245 TEMPERATURES MAT
Status Display EDT Evaporator Discharge Tmp NO XXX.X F -40 TO 245 TEMPERATURES EDT
Status Display RAT Return Air Temperature YES XXX.X F -40 TO 245 TEMPERATURES RAT
Status Display OAT Outside Air Temperature YES XXX.X F -40 TO 245 TEMPERATURES OAT
Status Display ECONOPOS Econo Damper Current Pos NO XXX % 0-100% OUTPUTS EC.AP
Status Display SLO_CHNG Slow Change Cap Override YES ON/OFF — On/Off — —
Status Display LOW_TEMP Low Temp Cap Override YES ON/OFF — On/Off — —
Status Display HI_TEMP High Temp Cap Override YES ON/OFF — On/Off — —
Status Display PULLDOWN Pull Down Cap Override YES ON/OFF — On/Off — —