APPENDIX A — CCN POINTS (cont)
CONFIG — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration PURGEN IAQ Purge YES Enable/Disable Enable/Disable CONFIGURATION PRG.E
Configuration IQPD IAQ Purge Duration YES X.X MIN 5 TO 60 CONFIGURATION PRG.D
Configuration UEFC_CFG Unocc. Free Cool Config YES 0,1,2
0 = disabled, 1= all the time,
2= x time before occupied
CONFIGURATION UFC.C
Configuration UEFCTIME Unocc. Free Cool Time YES XXX MIN 0 TO 720 CONFIGURATION UFC.T
Configuration HTOCCENA Occupied Heating Enabled YES Yes/No Yes/No CONFIGURATION OCC.H
Configuration RSEN Space Temperature Reset YES Enable/Disable Enable/Disable
Configuration STATICFG Static P Control YES 0,1 0=None, 1=VFD Control CONFIGURATION SP.C
Configuration FANM Fan Mode (0=Auto, 1=cont) YES 0,1 0=Auto, 1 = Continuous CONFIGURATION FAN.M
Configuration KCOOL TCST Cool Time/Temp Fact YES XX MIN 0 TO 60 CONFIGURATION C.TC.F
Configuration KHEAT TSCT Heat Time/Temp Fact YES XX MIN 0 TO 60 CONFIGURATION H.TC.F
Configuration SAMPMINS VAV Unoc.Fan Retry Time YES XX MIN 0 TO 60 CONFIGURATION SAMP
Configuration rmt.c Remote Switch Config YES 0,1,2
0=None, 1=Occupancy,
2=Start/Stop
CONFIGURATION RMT.C
COOL_CFG — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration CMPA1ENA Enable Compressor A1 YES Enable/Disable Enable/Disable CONFIGURATION A1.EN
Configuration CMPA2ENA Enable Compressor A2 YES Enable/Disable Enable/Disable CONFIGURATION A2.EN
Configuration CMPB1ENA Enable Compressor B1 YES Enable/Disable Enable/Disable CONFIGURATION B1.EN
Configuration CMOB2ENA Enable Compressor B2 YES Enable/Disable Enable/Disable CONFIGURATION B2.EN
Configuration MLV_SEL Minimum Load Valve? YES YES/NO YES/NO CONFIGURATION S.MLV
Configuration CSB_A1EN CSB A1 Feedback Alarm YES Enable/Disable Enable/Disable CONFIGURATION A1.C.E
Configuration CSB_A2EN CSB A2 Feedback Alarm YES Enable/Disable Enable/Disable CONFIGURATION A2.C.E
Configuration CSB_B1EN CSB B1 Feedback Alarm YES Enable/Disable Enable/Disable CONFIGURATION B1.C.E
Configuration CSB_B2EN CSB B2 Feedback Alarm YES Enable/Disable Enable/Disable CONFIGURATION B2.C.E
Configuration OATLCOMP Compressor Lockout Temp YES XXX.X F -20 TO 40 CONFIGURATION C.L.OA
Configuration COOL_FOD Fan-off Delay, Mech Cool YES XXX SEC 0 TO 600 CONFIGURATION C.L.OA
Configuration CTRENDLV Cool Trend Demand Level YES XXXX F 0.1 TO 5.0 CONFIGURATION CT.LV
CTRL_ID — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration Device Name YES XXXXXXXX text field
Configuration Description YES XXXXXXXXXXXXX text field
Configuration Location YES XXXXXXXXXXXXX text field
Configuration Software Part Number NO NOT USED
Configuration Model Number NO NOT USED
Configuration Serial Number NO NOT USED
Configuration Reference Number NO NOT USED
DISPLAY — CONTROLLER
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Configuration PASSWORD Service Password YES XXXX 1111 is default CONFIGURATION PSWD
Configuration PA S S_EBL Password Enable YES Enable/Disable Enable/Disable CONFIGURATION PROT
Configuration DISPUNIT Metric Display YES On/Off On/Off CONFIGURATION METR
Configuration LANGUAGE Language Selection YES 0,1,2,3,4
0=English, 1= Spanish,
2= French, 3= Portugese
CONFIGURATION LANG