APPENDIX A — CCN POINTS (cont)
DISLOGIC — DIAGNOSTICS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Service Configuration FLTSLOGC Filter Status YES Open/Closed Open/Closed INPUTS FIL.S
Service Configuration GASFANLG IGC Feedback YES Open/Closed Open/Closed INPUTS GAS.F
Service Configuration FSDKOGIC Fireshutdown YES Open/Closed Open/Closed INPUTS FDWN
Service Configuration ECOSWLOG Economizer Switch YES Open/Closed Open/Closed INPUTS E.ENA
Service Configuration RMTINLOG Remote Switch YES Open/Closed Open/Closed INPUTS RE.MT
Service Configuration IAQINLOG IAQ Disc.Input YES Open/Closed Open/Closed INPUTS I.AQS
Service Configuration SFSLOGIC Fan Status Sw. YES Open/Closed Open/Closed INPUTS FAN.S
Service Configuration DMD_SW1L Dmd.Lmt.Sw.1 YES Open/Closed Open/Closed INPUTS DLM.1
Service Configuration DMD_SW2L Dms.Lmt.Sw2 YES Open/Closed Open/Closed INPUTS DLM.2
Service Configuration PRESLOGC Press. Switch YES Open/Closed Open/Closed INPUTS F.PRS
Service Configuration EVACLOGC Evaculation Sw. YES Open/Closed Open/Closed INPUTS F.EVC
Service Configuration PURGLOGC Smoke Purge Sw. YES Open/Closed Open/Closed INPUTS F.PRG
SENSCNFG — DIAGNOSITCS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Service Configuration SPT_TRIM SPT Trim YES XXX.X F -10.0 TO 10.0 TEMPERATURES SPT.T
Service Configuration SAT_TRIM SAT Trim YES XXX.X F -10.0 TO 10.0 TEMPERATURES SAT.T
Service Configuration OAT_TRIM OAT Trim YES XXX.X F -10.0 TO 10.0 TEMPERATURES OAT.T
Service Configuration RAT_TRIM RAT Trim YES XXX.X F -10.0 TO 10.0 TEMPERATURES RAT.T
Service Configuration SGT_TRIM Staged Gas LAT Avg Trim YES XXX.X F -30.0 T0 30.0 TEMPERATURES SGT.T
Service Configuration CTA_TRIM Condensing Temp A Trim YES XXX.X F -30.0 T0 30.0 TEMPERATURES CTA.T
Service Configuration CTB_TRIM Condensing Temp B Trim YES XXX.X F -30.0 T0 30.0 TEMPERATURES CTB.T
Service Configuration SPA_TRIM Suction Pressure A Trim YES XXX.X PSI -50.0 TO 50.0 PRESSURES SP.A.T
Service Configuration SPB_TRIM Suction Pressure B Trim YES XXX.X PSI -50.0 TO 50.0 PRESSURES SP.B.T
Service Configuration DPA_TRIM Dischrg Pressure A Trim YES XXX.X PSI -50.0 TO 50.0
Service Configuration DPB_TRIM Dischrg Pressure B Trim YES XXX.X PSI -50.0 TO 50.0
Service Configuration BP_TRIM Building Pressure Trim YES XX.XX in H2O -10.0 TO 10.0 PRESSURES BP.T
Service Configuration BP_RANGE Bldg Press (+/-) Range YES XX.XX in H2O 0 TO 1.00 CONFIGURATION BP.R
Service Configuration SP_TRIM Static Press Trim YES XX.XX in H2O -10.0 TO 10.0 PRESSURES DSP.T
Service Configuration SP_LOW Duct Press Sensor Lo End YES XXX.XX -10.0 TO 10.0 CONFIGURATION SP.L.L
Service Configuration SP_HIGH Duct Press Sensor Hi End YES XXX.XX -10.0 TO 10.0 CONFIGURATION SP.H.L