Elta T210 Specifications Page 78

  • Download
  • Add to my manuals
  • Print
  • Page
    / 150
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 77
78
BUILDING PRESSURE SENSOR HIGH END (BPHL)
This is used to configure the building pressure value that will
correspond to a 20 mA signal from the sensor.
BUILDING PRESSURE SENSOR LOW END (BPLL)
This is used to configure the building pressure value that will
correspond to a 4 mA signal from the sensor.
BP THRESHOLD ADJUSTMENT (BP.ZG) — This is a
factor that is used to adjust the control PID loop. Normally this
should not have to be adjusted.
BP PID EVALUATION (BP.DT) — This is a PID loop
adjustment factor. Do not change this without direction from
Application Engineering.
HIGH BP LEVEL (BP.HP) — This is the high limit for the
routine 2 at which a fan stage will be added. Do not change this
value.
LOW BP LEVEL (BP.LP) — This is the low limit for the
routine 2 at which a fan stage will be removed. Do not change
this value.
Space Temperature Offset The control provides
capability for CV units to offset a space temperature set point
by ± 1 to10 F, using a T56 device. The T56 slider analog input
is linearized by the software into the –(1-10) to +(1-10) F
range, and uses the STO.R configuration to set the range which
is located in the CONFIGURATION-OPTS submenu and the
Space Temperature Offset (SPTO) read the offset value. The
SPTO can be read in the TEMPERATURE-UNIT submenu.
The SPTO offset is applied to the error term during the
occupied period only.
It will be applied as follows:
The error term equals the occupied set point (OCSP or
OHSP) + SPTO – SPT.
NOTE: This must be used with HVACSPT2 control.
Temperature Compensated Start — This logic is
used when the unit is in unoccupied state. It will calculate early
Start Bias time based on Space Temperature deviation from
occupied set points. This will allow the control to learn when to
start the unit so that the space is at conditioned levels when the
occupied period starts. This is required for ASHRAE 90.1
compliance.
The following conditions must be met for the algorithm to
run:
Unit in unoccupied state
Next occupied time is valid
Current time of day is valid
Valid Space Temperature reading is available (sensor or
DAV-Linkage)
The algorithm will calculate Start Bias time (BIASTIME) in
minutes using the following equations:
If (space temperature > occupied cooling set point)
BIASTIME = (space temperature occupied cooling set
point)* C.TC.F
If (space temperature < occupied heating set point)
BIASTIME = (occupied heating set point space tempera-
ture)* H.TC.F
When BIASTIME > 0 the algorithm will subtract it from
the next occupied time to calculate the new start time. When
the new start time is reached, the Temperature Compensated
Start mode is set, the fan is started and the unit controlled as in
occupied state. Once set, Temperature Compensated Mode will
stay on until the unit goes into occupied mode. The Start Bias
Time will be written into the Linkage Equipment Table if the
unit is controlled in DAV mode.
If Unoccupied Economizer Free Cool mode is active
(MODEUEFC) when Temperature Compensated Start begins,
the Unoccupied Free Cool mode will be stopped.
The following configurations are required for this logic:
TCST COOL TIME/TEMP FACT (C.TC.F) — This is located
in the CONFIGURATION-COOL submenu and is the factor
for the start time bias equation for cooling.
TCST HEAT TIME/TEMP FACT (H.TC.F) — This is located
in the CONFIGURATION-HEAT submenu and is the factor
for the start time bias equation for heating.
Smoke Control Modes — There are four smoke con-
trol modes that can be used to control smoke within areas
serviced by the unit: Pressurization Mode, Evacuation Mode,
Smoke Purge Mode, and Fire Shutdown. Evacuation, Pressur-
ization and Smoke Purge modes require the Controls Expansion
Board (CEM). The Fire Shutdown input is located on the main
board (MBB) on terminals TB5-10 and TB5-11. The unit may
also be equipped with a factory-installed return air Smoke
Detector that is wired to TB5-10,11 and will shut the unit down
if a smoke condition is determined. On terminal TB5-8 and 9,
field-monitoring wiring can be connected to also monitor the
smoke detector.
Once in a fire shutdown condition, additional inputs on the
CEM board can be used to put the unit in the Pressurization,
Evacuation, and Smoke Purge Modes. These switches or inputs
are connected to TB6 as shown below and on Fig. 7.
Pressurization — TB5-12 and 13
Evacuation — TB5-13 and 14
Smoke Purge — TB5-13 and 15
Each mode must be energized individually on discrete
inputs and the corresponding alarm is initiated when a mode is
activated. The fire system provides a normally closed dry
contact closure.
FIRE SHUTDOWN MODE — This mode causes the com-
plete shutdown of the unit.
PRESSURIZATION MODE This mode attempts to raise
the pressure of a space to prevent smoke infiltration from
another space. The space with smoke should be in an
Evacuation Mode attempting to lower its pressure. Opening the
economizer (thereby closing the return air damper), shutting
down power exhaust and turning the indoor fan on will
increase pressure in the space.
EVACUATION MODE — This mode attempts to lower the
pressure of the space to prevent infiltrating another space with
its smoke. Closing the economizer (thereby opening the return
air damper), turning on the power exhaust and shutting down
the indoor fan decrease pressure in the space.
SMOKE PURGE MODE This mode attempts to draw out
smoke from the space after the emergency condition. Opening
the economizer (thereby closing the return air damper), turning
on both the power exhaust and indoor fan will evacuate smoke
and bring in fresh air.
The following configurations apply to the fire and smoke
control operation.
IDF SPEED IN FIRE MODE (SF.FS) — This is the VFD
speed that will be used when the fire pressurization and purge
modes are enabled. To use this, the unit must be configured
with the Static Pressure Control (SP.C) variable set to VFD
control. This method should be used instead of tying in to the
VFDs which also have a means for fire override control.
EVACUATION SW NORMALLY (EVC.L) — This is located
in the CONFIGURATION-SW.LG submenu and is used to
configure the normally open/closed status of the switch.
FILTER STATUS NORMALLY (FTS.L) — This is located
in the CONFIGURATION-SW.LG submenu and is used to
configure the normally open/closed status of the switch.
FIRE SHUTDOWN NORMALLY (FSD.L) — This is located
in the CONFIGURATION-SW.LG submenu and is used to
configure the normally open/closed status of the switch.
Page view 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 149 150

Comments to this Manuals

No comments